Lorem Ispum

Ther­mo De­tec­tor Gre­Con TM 3/9 plus

Protect against the risk of fire in industrial processes caused by overheating machinery

Key benefits

  • Individually configurable trigger thresholds for pre-alarm and main alarm Individual control of individual relay outputs

  • Graphical monitoring of the temperature evolution for each probe with GreCon TOUCH control console.

  • Simultaneous temperature monitoring at three different points with eyelet or screw PT1000 probes.

  • Real-time detector status via LEDs.

  • Intelligent detector with extended internal monitoring.

Functional description

The heat detector TM 3/9 plus is a sensor for the simultaneous detection of temperatures in a maximum of three different areas. The temperature alarm threshold is not a fixed value and can be set in a wide range and may be configured using the GreCon Configurator tool. If the temperature at the measuring point exceeds the configured threshold temperature, then an alarm signal is sent to the control console and this signal is active until the temperature falls below the threshold value.

The detector can be connected to every GreCon control console using a standard three core cable.  A range of flexible mounting adapter options exist to suit any environment. The control console interfaces with the detector for monitoring of ignition sources within the process, configuration of detection parameters and automated check of the detector’s correct function.

Technical specification

Summary

Temperature monitoring by means of three contact temperature probes to monitor facilities for mechanical malfunctions. Two configurable alarm thresholds.

Specifications

  • Supply voltage: 13 V to 30 V DC

  • Current drawn: min. 3 mA to max. 30 mA

  • Temperature switching points: +60 °C to max. +200 °C

  • Ambient temperature range: ex-free zone -40 °C to +85 °C, ex-zone -20 °C to +60 °C

  • Process temperature range: ex-free zone -40 °C to +340 °C, ex-zone -20 °C to +60 °C

  • Storage temperature: -20 °C to +60 °C

  • Relative humidity: 0 to 95 %, non-condensing

  • Status indication, alarm: position 1: LED = red steady light

  • Status indication, operation: position 2: two-colour LED = green steady light

  • Status indication, fault: position 2: two-colour LED = yellow steady light

  • Application area: dust explosive zone 20

  • Protection class: IP 66

  • Connection: pre-fitted pluggable connecting cable

  • Number of wires/wire cross section: 3 x 0.5 mm²

  • Cable length: 2.5 m, 25 m (optionally)

  • Material of housing: aluminium die casting (GD-AlSi12)

  • Housing dimensions: 84 mm x 84 mm x 31 mm

  • Housing colour: orange (RAL 2004), lacquered

  • Number of probes: 1, 2 or 3

  • Sensing element: PT 1000

We look forward to hearing from you.

Please fill in all mandatory fields marked with an asterisk (*).