Lorem Ispum

Fire Traps

Mechanically seal transport channels and protect the downstream material flow from ignition

Technical specification

Summary

The fire trap is an additional element of the GreCon Spark Extinguishing System. In case of an alarm, the fire trap closes a transport duct mechanically.

Specifications

  • Area of application: negative and positive pressure ducts, suitable for corrosive media and for use in the food industry
  • Material: steel, stainless steel on request
  • Release: electropneumatially via control console
  • Drive: pneumatic drive by air cylinder, incl. protective grating
  • Closing time: 0.1 to 0.4 s, depending on nominal width
  • Compressed air supply: 4 to 6 bar, to be provided by the customer
  • Control: automatic release via control console, closure of the transport system upon release of the fire trap